4-15
Group 01: V/F Control Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
01-00
V/F Curve
Selection
0~FF
F
-
O
O
X
X
X
X
O
*3
01-01
Reserved
01-02
Maximum Output
Frequency of
Motor 1
5.0~599.0
60.0
Hz
O
O
O
O
O
O
O
01-03
Maximum Output
Voltage of Motor
1
230V: 0.1~255.0
220.0
V
O
O
X
X
X
X
O
460V: 0.2~510.0
440.0
575V: 0.1~670.0
575.0
690V: 0.1~804.0
690.0
01-04
Middle Output
Frequency 2 of
Motor 1
0.0~599.0
0.0
Hz
O
O
X
X
X
X
O
01-05
Middle Output
Voltage 2 of
Motor 1
230V: 0.0~255.0
0.0
V
O
O
X
X
X
X
O
460V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-06
Middle Output
Frequency 1 of
Motor 1
0.0~599.0
3.0
Hz
O
O
X
X
X
X
O
01-07
Middle Output
Voltage 1 of
Motor 1
230V: 0.0~255.0
*
V
O
O
X
X
X
X
O
460V: 0.0~510.0
575V: 0.0~670.0
690V: 0.0~804.0
01-08
Minimum Output
Frequency of
Motor 1
0.0~599.0
VF:1.5
Hz
O
O
O
O
O
O
O
VF+PG:
1.5
SLV:
0.6
SV:0.1
PMSV:
0.1
PMSLV
:9.0
SLV2:
1.0
01-09
Minimum Output
Voltage of Motor
1 (for 3~30HP)
230V: 0.0~255.0
7.5
V
O
O
X
X
X
X
O
460V: 0.0~510.0
15.0
575V: 0.0~670.0
690V: 0.0~804.0
01-10
Torque
Compensation
Gain
0.0~2.0
0.5
-
O
O
X
X
X
X
O
*1
01-11
Selection of
Torque
Compensation
Mode
0: Torque
Compensation Mode
0
0
-
O
O
X
X
X
X
X
1: Torque