4-174
Table
4.4.12
Selection of analog output terminals function (04-11 and 04-16)
04-11, 04-16
Parameter
setting
Function
(Keypad display)
Monitoring
Parameters
Group 12
Control Mode
VF VF+PG SLV
SV
PM
SV
PM
SLV
SLV2
0
Output Freq
12-17
O
O
O
O
O
O
O
1
Freq Ref
12-16
O
O
O
O
O
O
O
2
Output Voltage
12-19
O
O
O
O
O
O
O
3
DC Voltage
12-20
O
O
O
O
O
O
O
4
Output Current
12-18
O
O
O
O
O
O
O
5
Output KW
12-21
O
O
O
O
O
O
O
6
Motor Speed
12-22
O
O
O
O
O
O
O
7
Output PF
12-23
O
O
O
O
O
O
O
8
AI1 Input
12-25
O
O
O
O
O
O
O
9
AI2 Input
12-26
O
O
O
O
O
O
O
10
Torque Ref
12-27
X
X
O
O
O
O
X
11
Current Iq
12-28
X
X
O
O
O
O
X
12
Current Id
12-29
X
X
O
O
O
O
X
13
Speed Deviation
12-30
X
X
X
O
O
X
X
14
Reserved
X
X
X
X
X
X
X
15
ASR Output
12-32
X
O
X
O
O
X
X
16
Reserved
-
X
X
X
X
X
X
X
17
Voltage Ref Vq
-
X
X
O
O
O
O
X
18
Voltage Ref Vd
-
X
X
O
O
O
O
X
19
Reserved
-
X
X
X
X
X
X
X
20
Reserved
-
X
X
X
X
X
X
X
21
PID Input
12-36
O
O
O
O
O
O
O
22
PID Output
12-37
O
O
O
O
O
O
O
23
PID Setpoint
12-38
O
O
O
O
O
O
O
24
PID Feedback
12-39
O
O
O
O
O
O
O
25
Output Freq (SFS)
-
O
O
O
O
O
O
O
26
PG Feedback
12-33
X
O
X
O
O
X
X
27
Reserved
-
X
X
X
X
X
X
X
28
Comm Control
-
O
O
O
O
O
O
O
04-19
AO2 Output Signal Type
Range
0: AO2 0~10V
1: AO2 4~20mA
Use SW6 on the conrtol board to select AO2 analog output type.
When 04-19=0 (AO2 is 0~10V) and SW6 on the control board set to V, AO2 output signal type is voltage.
When 04-19=1 (AO2 is 4~20mAV) and SW6 on the control board set to I, AO2 output signal type is set to current.
04-20
Filter Time of AO Signal Scan
Range
0.00~0.50 Sec
Parameter set analog output filter time to enhance interference. Please note increasing the filter time decreases
analog output response time.