4-49
Group 12: Monitoring Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
12-02
PID Feedback
Display Unit
Setting (LED)
0: xxxxx (no unit)
0
O
O
O
O
O
O
O
*6
1: xxxPb (pressure)
2: xxxFL (flow)
12-03
Line Speed
Display (LED)
0~65535
1500/
1800
RPM
O
O
O
O
O
O
O
*1
*6
12-04
Modes of Line
Speed Display
(LED)
0: Display Inverter Output
Frequency
0
-
O
O
O
O
O
O
O
*1
*6
1: Display Line Speed
with integer (xxxxx)
2: Display Line Speed
with the First Decimal
Place (xxxx.x)
3: Display Line Speed
with the Second
Decimal Place (xxx.xx)
4: Display Line Speed
with the Third Decimal
Place (xx.xxx)
12-05
Status Display of
Digital Input
Terminal (LED /
LCD)
LED display is shown as
below
no input
correspondences to input
and output
LCD display is shown as
below
-
O
O
O
O
O
O
O
12-06
~
12-10
Reserved
S1 S2 S3 S4S5 S6 S7 S8
R1
R2
DO1
0
0
0
0
0
0
0 0
Input Terminal(S8)
Input Terminal(S7)
Input Terminal(S6)
Input Terminal(S5)
Input Terminal(S4)
Input Terminal(S3)
Input Terminal(S2)
Input Terminal(S1)
0:OPEN
1:CLOSE
0
0
0
Output Terminal(DO1)
Output Terminal(R2)
Output Terminal(R1)