4-262
17-Automatic Tuning Parameters
17-00
Mode selection of automatic tuning
Range
0:
Rotational auto-tuning
1:
Static auto-tuning
2:
Stator resistance measurement
3:
Reserved
4:
Loop tuning
5:
Rotational Auto-tuning Combination (Item: 4+2+0)
6:
Static Auto-tuning Combination (Item: 4+2+1)
17-01
Motor rated output power
Range
0.00~600.00 kW
17-02
Motor rated current
Range
For VF, VF+PG modes, 10%~200% of the inverter rated current
For SLV, SV modes, 25%~200% of the inverter rated current.
17-03
Motor rated voltage
Range
200V:50.0~240.0 V
400V:100.0~480.0 V
575V:150.0~670.0 V
690V: 180.0~804.0 V
17-04
Motor rated frequency
Range
5.0~599.0 Hz
17-05
Motor rated speed
Range
0~24000 rpm
17-06
Pole number of motor
Range
2~16 pole
17-07
Number of PG pulse
Range
0~60000 PPR
17-08
Motor no-load voltage
Range
50~240 V: 200V
100~480 V: 400V
575V: 420~600 V
690V:504~720 V
17-09
Motor excitation current
Range
15~70% motor rated current
17-10
Automatic tuning start
Range
0:
Disable
1:
Enable