4-252
13-08=6:
2-wire initialization (200V/380V/575V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Figure 4.4.1.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class)
13-08=7:
3-wire initialization (200V/380V/575V)
Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are set for
3-wire start operation and stop command.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class)
13-08=8:
PLC initialization
Clear built-in PLC ladder logic and related values.
13-08=9:
2 wire Initialization (60Hz) (220/440V)
The same as 13-08=2
13-08=10:
3 wire Initialization (60Hz) (220/440V)
The same as 13-08=3
Parameters
don’t be influenced by Restore factory setting / Initialize (13-08)
No.
parameters
00-00
Control Mode Selection
00-04
Language
00-27
HD/ND Mode Selection
***
01-00
V/F Curve Selection
01-26
V/F Curve Selection of Motor 2
13-00
Inverter Capacity Selection
13-03
Cumulative Operation Hours 1
13-04
Cumulative Operation Hours 2
13-05
Selection of Cumulative Operation Time
13-09
Fault history clearance function
Range
0:
Do not clear fault history
1:
Clear fault history
13-09=1:
Clears inverter fault history.
Note: parameters 12-11~12-15/12-45~12-64 are cleared as well.