![TECO-Westinghouse A510 Instruction Manual Download Page 245](http://html.mh-extra.com/html/teco-westinghouse/a510/a510_instruction-manual_1072531245.webp)
4-170
100
%
-10V
10V
(20mA)
0V
(4mA)
Frequency
Reference
Lower Bound
Terminal AI2
analog input
Figure 4.4.47 Adjustment of lower limit of frequency reference
04-05=9:
Jump frequency 4
Multi-function analog input AI2 can be used to adjust Jump frequency 4.
Maximum output frequency (01-02, Fmax) = 100%. Setting 11-08 to 11-10 to 0.0Hz turns of the Jump frequency
function.
100%
-
10V
10V
(20mA)
0V
(4mA)
Jump
Frequency 4
Terminal AI2
analog input
Output
Frequency
Jump
Frequency
Reference
Using
analog
input
Jump
Freq 3
(11-10)
Jump
Freq 2
(11-09)
Jump
Freq 1
(11-08)
(a) Jump Frequency 4 Adjustment
(b) Jump Frequency Hierarchy
Jump
Freq 4
Figure 4.4.48 Jump frequency 4 Setting Operation
04-05=10:
Added to AI1