4-47
Group 11: Auxiliary Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
11-46
Frequency Hold
Time at Stop
0.0~10.0
0.0
s
O
O
O
O
O
O
O
11-47
KEB Deceleration
Time
0.0~25.5
0.0
s
O
O
X
X
X
X
O
*1
11-48
KEB Detection
Level
230V: 190~210
200
V
O
O
X
X
X
X
O
460V: 380~420
400
575V: 540~570
555
690V: 540~684
555
11-49 Zero-servo Gain
0~50
5
-
X
X
X
O
O
X
X
11-50 Zero-servo Count 0~4096
12
-
X
X
X
O
O
X
X
11-51
Braking Selection
of Zero Speed
0: Disable
0
-
O
X
X
X
X
X
O
1: Enable
11-52
Droop Control
Level
0.0~100.0%
0.0
%
X
X
X
O
O
X
X
*1
11-53
Droop Control
Delay
0.01~2.00
0.2
s
X
X
X
O
O
X
X
*1
11-54
Initialization of
Cumulative
Energy
0: Do not Clear
Cumulative Energy
0
-
O
O
O
O
O
O
O
*1
1: Clear Cumulative
Energy
11-55
STOP Key
Selection
0: Stop Key is Disabled
when the Operation
Command is not
Provided by Operator.
1
-
O
O
O
O
O
O
O
1: Stop Key is Enabled
when the Operation
Command is not
Provided by Operator.
11-56
UP/DOWN
Selection
0: When O
perator’s
UP/DOWN is Disabled,
it will be Enabled if
Press ENTER after
Frequency
Modification.
0
-
O
O
O
O
O
O
O
1: When O
perator’s
UP/DOWN is Enabled,
it will be Enabled after
Frequency
Modification.
11-57
Reserved
11-58
Record Reference
Frequency
0: Disable
0
-
O
O
O
O
O
O
O
*1
1: Enable
11-59
Gain of Preventing
Oscillation
0.01~2.50
*
O
O
X
X
X
X
O
11-60 Upper Limit of
0~100
*
%
O
O
X
X
X
X
O