4-176
Example:
Acceleration / deceleration timing when 05-00 is set to 1. In this example the following parameters are
set:
00-02=1
(External Terminal Operation
)
03-00=0
(Terminal S1: Forward /Stop)
03-01=1
(Terminal S2: Reversal /Stop)
03-02=2
(Terminal S3: Speed 1)
03-03=3
(Terminal S4: Speed 2)
03-03=4
(Terminal S5: Speed 3)
*Speed 1 is required to confirm if AI2 function setting (04-05) is set to 0 (Auxiliary frequency). If 04-05=0, it will
make the frequency of speed 1 set to AI2 auxiliary frequency and the value is determined by AI2. If function of
speed 1 is generally used, set AI2 to other functions except 0 (the recommended value: set 10 ADD to AI1.)
Acceleration / Deceleration Calculation Mode 1:
If the run command is cycled on and off, acceleration and deceleration time (a ~ f) is calculated based on the
active speed command as follows:
Terminal S1
Terminal S2
Terminal S3
Terminal S4
Run
Run
Run
Stop
Stop
Stop
Off
Off
Off
Off
On
On
a
b
c
d
e
f
S
p
e
e
d
C
o
m
m
a
n
d
0
S
p
e
e
d
C
o
m
m
a
n
d
1
S
p
e
e
d
C
o
m
m
a
n
d
2
05-01
05-02
05-03
T
Hz
in sec.
(05-17) x (05-01)
(05-18) x (05-01)
(05-19) x (05-02)
(01-02)
(01-02)
(01-02)
a =
b =
c =
(05-20) x (05-02)
(05-21) x (05-03)
(05-22) x (05-03)
(01-02)
(01-02)
(01-02)
d =
e =
f =
in sec.