![TECO-Westinghouse A510 Instruction Manual Download Page 135](http://html.mh-extra.com/html/teco-westinghouse/a510/a510_instruction-manual_1072531135.webp)
4-60
Group 17: Automatic Tuning Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F+
PG
SLV SV
PM
SV
PMS
LV
SLV2
17-00
Mode Selection of
Automatic Tuning*
0: Rotation Auto-tuning
VF:2
VF+PG
:2
SLV:6
SV:6
SLV2:6
-
O
O
O
O
X
X
O
1: Static Auto-tuning
2: Stator Resistance
Measurement
3: Reserved
4: Loop Tuning
5: Rotation Auto-tuning
Combination (item:
4+2+0)
6: Static Auto-tuning
Combination (item:
4+2+1)
17-01
Motor Rated
Output Power
0.00~600.00
KVA
KW
O
O
O
O
X
X
O
17-02
Motor Rated
Current
0.1~1200.0
KVA
A
O
O
O
O
X
X
O
17-03
Motor Rated
Voltage
230V: 50.0~240.0
220
V
O
O
O
O
X
X
O
460V: 100.0~480.0
440
575V:150.0~670.0
575
690V: 180.0~804.0
690
17-04
Motor Rated
Frequency
5.0~599.0
60.0
Hz
O
O
O
O
X
X
O
17-05
Motor Rated
Speed
0~24000
KVA
rpm
O
O
O
O
X
X
O
17-06
Pole Number of
Motor
2~16 (Even)
4
Pole O
O
O
O
X
X
O
17-07 PG Pulse Number 0~60000
1024
ppr
O
O
O
O
X
X
O
17-08
Motor no-load
Voltage
230V: 50~240
-
V
O
O
O
O
X
X
O
460V100~480
575V: 420~600
690V:504~720
17-09
Motor Excitation
Current
0.01~600.00
-
A
X
X
O
O
X
X
X
17-10
Automatic Tuning
Start
0: Disable
0
-
O
O
O
O
X
X
O
1: Enable
17-11
Error History of
Automatic Tuning
0: No error
0
-
O
O
O
O
X
X
O
1: Motor data error
2: Stator resistance
tuning error
3: Leakage induction
tuning error
4: Rotor resistance tuning
error
5: Mutual induction tuning
error
6: Encoder error
7: DT Error