![TECO-Westinghouse A510 Instruction Manual Download Page 170](http://html.mh-extra.com/html/teco-westinghouse/a510/a510_instruction-manual_1072531170.webp)
4-95
00-32=6: Hoist* Consult TECO for the detailed settings
Parameter
Name
Value
00-00
Control mode selection
2: SLV
00-05
Main Frequency command source selection
0: keypad
11-43
Hold Frequency at start
3.0 Hz
11-44
Frequency hold Time at start
0.3 sec
00-14
Acceleration time 1
3.0 sec
00-15
Deceleration time 1
3.0 sec
11-01
Carrier frequency
5.0kHz
05-01
Frequency setting of speed-stage 0
6.0 Hz
05-02
Frequency setting of speed-stage 1
30.0 Hz
05-03
Frequency setting of speed-stage 2
60.0 Hz
03-28
Photo-coupler output
5 : frequency detection 2
07-18
Minimum baseblock time
0.3 sec
08-00
Stall prevention function
xx1x: Stall prevention ineffective in
deceleration
03-13
Frequency detection level
2.0 Hz
03-14
Frequency detection width
0.0 Hz
08-18
Selection of low-torque operation
0: Deceleration to stop
08-19
Level of low-torque detection
2 %
08-20
Time of low-torque detection
0.5 sec
08-09
Selection of input phase loss protection
1 : Enable
08-10
Selection of output phase loss protection
1 : Enable