4-134
03-0X =32:
Sync command
Selects between frequency reference source from pulse input or frequency reference source selected by
parameter 00-05. Refer to page 4-116 for more information.
Input
Ref. Source
Frequency Reference / Run/Stop Command Source
ON
Pulse Input
- Frequency reference set by pulse input
OFF
Parameter 00-05 - Frequency reference source selected by parameter 00-05
Note:
- Function is disabled when the Local/Remote selection (25) or Remote mode selection (26) is active.
- To switch between local and remote the inverter has to be stopped.
03-0X =33:
DC braking
When input is active DC-Injection braking is enabled during start and stopping of the inverter.
DC Injection braking is disabled when a run or jog command is active. Refer to the DC braking time diagram in
Figure 4.4.24.
DC
injection
Brake
DC
injection
Brake
t
01-08
(Fmin)
Fout > 01-08 (Fmin)
Fout > 07-06 (DC-Inj Start Freq.)
Run Or Jog
Command
DC injection
Braking
Command
Output
Frequency
OFF
ON
OFF
ON
t
t
07-06
(Fdc-inj)
Figure 4.4.24 DC braking timing diagram
03-0X =35:
Timing function
Refer to the "time function" parameter 03-37 and 03-38.
03-0X =36:
PID Soft start disable
Refer to the "PID Control" function of PID function parameter group 10.
03-0X =37:
Traverse operation
03-0X =38:
Upper Deviation of traverse operation
03-0X =39:
Lower Deviation of traverse operation
See “Wobble Frequency” function in parameter group 19
03-0X =40:
Switching between motor 1 and motor 2