4-300
22- PM Motor Parameters
22-00
PM motor rated power
Range
0.00~600.00 Kw
22-02
PM motor rated current
Range
25%~200% inverter’s rated current
22-03
PM motor’s pole number
Range
2~96 Poles
22-04
PM Motor’s rated rotation speed
Range
1~60000 rpm
22-05
PM motor’s maximum rotation speed
Range
1~60000 rpm
22-06
PM motor rated frequency
Range
0.1~599.0 Hz
The PM parameter group can be restored to factory default be initializing the inverter (13-00).
(01) PM motor rated power (22-00)
Set the motor power according to the motor nameplate.
(02) PM motor rated current (22-02)
Set the motor full load according to the motor nameplate.
(03) PM motor pole number (22-03).
Set the number of motor poles according to the motor nameplate.
(04) PM motor rated speed (22-04)
Set parameter 22-04 or 22-06, the inverter will automatically calculate the one or the other.
Set the motor rated speed in rpm according to the motor nameplate.
Note:
Only set parameter 22-04 or 22-06, the inverter will automatically calculate the other one.
Formula: n (22-04) = 120*f (22-06) / P(22-03)
(05) PM motor maximum rotation speed (22-05)
Set the maximum motor rated speed in rpm according to the motor nameplate.
(06) PM motor rated frequency (22-06)
Set the motor rated frequency according to the motor nameplate.