4-80
S1
S2
S5 Stop
(On: Stop)
24VG
Momentary switches
(Push buttons)
Reverse Run Command
(On: Run Reverse)
Forward Run Command
(On: Run Forward)
Note:
Terminal S1, S2 and S5 must be closed for a minimum of 50ms to activate operation.
Note:
The inverter will display SE2 error when input terminals S1-S8 is set to 53 and 26 simultaneously.
Time
Forward
Command
Motor
Speed
>50 ms
OFF
Stop
Forward
Reverse
Stop
ON
OFF
ON
OFF
ON
OFF
>50 ms
ON
OFF
(Inverter On)
>50 ms
Reverse
Command
Stop
Command
Time
Time
Time
Forward
00-02=2: Communication control
The inverter is controlled by the RS-485 port. Refer to parameter group 9 for communication setup.
00-02=3: PLC control
The inverter is controlled by the inverter built-in PLC logic. Refer to section 4.5.