Control by Keypoint
Installer Manual -
TP16-256
7-12
7.4.3.3
DEACTIVATION OF BY-PASS WITH CODE
Enter a code enabled for by-pass (master or standard user code enabled for the programs armed) followed by the
number of the program to be reactivated in its integrity, e.g.:
+
66778
+
1
The LED of the program previously partset becomes lit.
7.4.4
SPECIAL OPERATING CONDITIONS
7.4.4.1
FALSE CODE ALARM
The alarm is released when 32 keys are pressed without entering a valid code.
In case of false code alarm, the red LED 6 general alarm starts blinking.
The keypad which the false code has been entered on is disabled for 2 minutes. Simultaneously, the buzzers of all
the consoles connected are activated and the OCG and key LED of all the key readers and consoles are blinking. To
stop the alarm introduce a valid key or enter a valid code (master or standard user code) on another control unit
connected.
7.3.4.2
SIMULTANEOUS ARMING BY SEVERAL CONTROL UNITS
During the arming process by console, all the electronic keypads are disabled.
When trying to arm the control panel in this situation by electronic keypad, the 3 LED on the keypad blink for
approximately 3 seconds.
7.4.4.3
AUTOMATIC BLOCK OF THE TELEPHONE CALLS
If enabled by the holder of the master code, on disarming of a program the active telephone channels are blocked
automatically.
7.4.4.4
GENERAL ALARM
If a general alarm is active (the corresponding LED is blinking), arming of the control panel is not permitted with code
unless the code is enabled for the by-pass of the general alarms.
7.4.5
ASSOCIATION PROGRAMS-KEYPOINTS
The installer can associate freely the programs (1 to 32) to the secondary control units (keypoints) as well as to the
consoles. Therefore, every program LED of the keypoints can be associated to any program of the system.
The LED are associated by default as follows:
KEY READER WITH MINI KEYPAD TP SK6N
z
LED 1 - Program 1
z
LED 2 - Program 2
z
LED 3 - Program 3
z
LED 4 - Program 4
z
LED 5 - Program 5
z
LED 6 - Program 6
KEY READER CONNECTED TO THE INTERFACE TP SKN
z
LED 1 - Program 1
z
LED 2 - Program 2
z
LED 3 - Program 3
ELECTRONIC KEYPAD TP SDN
z
LED 1 - Program 1
z
LED 2 - Program 2
z
LED 3 - Program 3
z
LED 4 - Program 4
If you introduce a key enabled for different programs than the key reader, arming is not attained.
The association programs-LED determines the sequence of arming, too.
WARNING
Outside the access periods associated the codes are not accepted by the control panel and any
attempt at acceding to the system will have no effect.
When trying to do so, the system ignores the command.
The green LED 5 remains lit and the red program LED remain off.
After 5 seconds, the electronic keypad returns to stand-by.
WARNING
It is possible to use only one control unit at a time.
Summary of Contents for TP16-256
Page 4: ...IV Installer Manual TP16 256...
Page 12: ...Index Installer Manual TP16 256 8...
Page 16: ...General Features Installer Manual TP16 256 1 4...
Page 18: ...Hardware Installer Manual TP16 256 2 2...
Page 30: ...Hardware Installer Manual TP16 256 2 14...
Page 46: ...Hardware Input Expansion Modules Installer Manual TP16 256 2A 16...
Page 50: ...Hardware Console Installer Manual TP16 256 2B 4...
Page 59: ...TP16 256 Installer Manual Output Expansion Modules Hardware 2D 5 ADDRESSES 6 TO 13...
Page 68: ...Hardware Programming Interfaces Installer Manual TP16 256 2E 6...
Page 70: ...Hardware Telephone Communicator with GSM Module Installer Manual TP16 256 2F 2...
Page 80: ...Hardware Wireless Expansion Modules Installer Manual TP16 256 2G 10...
Page 86: ...Set up Installer Manual TP16 256 3 6...
Page 91: ...TP16 256 Installer Manual Set up 3 11...
Page 184: ...Control by Console Installer Manual TP16 256 6 4 OPERATIONS WITHOUT CODE...
Page 196: ...Control by Console Installer Manual TP16 256 6 16...
Page 224: ...Technical Specifications Installer Manual TP16 256 8 14...
Page 226: ...Appendix A Transmission Protocols Installer Manual TP16 256 A 2...
Page 230: ...Appendix B Special Procedures Installer Manual TP16 256 B 2...
Page 242: ...Appendix B Special Procedures Installer Manual TP16 256 B 14...
Page 244: ...Appendix C Code Management Installer Manual TP16 256 C 2...
Page 247: ...TP16 256 Installer Manual Code Management Appendix C C 5...