TP16-256
- Installer Manual
Programming by Console
5-39
COMMUNICATION WITH THE WIRELESS CONSOLES
Permits testing of the communication between the control panel and the wireless
consoles.
The test takes approx. 8 seconds and checks the correct data transmission/reception
of all the wireless consoles associated to the control panel (max. 4).
Communication issues
On the display are viewed the communication issues separately for all four wireless
consoles (T1, T2, T3 and T4):
z
Yes
Communication (TX/RX) without errors
z
No
Communication (TX/RX) with negative issue
z
- - -
No wireless console associated to this position
Commands available
+
EXIT
to quit the submenu
5.22.2
ZONE TEST
Permits testing of the correct functioning of the wired as well as the wireless detectors
and the inputs they are associated to.
On initiation of the test, the control panel disables both the general stand-by output
and that of the programs (detectors enabled).
On the display is viewed
Zones
followed by
- - -
for the entire duration of the test.
The control panel is waiting for signaling released by the zone inputs.
To verify correct functioning of the detectors and the inputs, pass by the detectors or
activate the contacts.
For every zone that is found open, the buzzer is activated on the consoles for approx.
2 seconds.
Test issue
After the test, pressing the arrow keys (
yw
) on the console, the zones that have
been found open are viewed in sequence.
Commands available
+
EXIT
to quit the submenu
5.22.3
INDOOR SIREN AND BATTERY TEST
On initiation of the test, the control panel reduces power supply voltage to 10.5V in
order to provoke the intervention of the battery.
The indoor sirens are activated while they are powered by battery.
The test takes 60 seconds and can be interrupted at any time by pressing the EXIT
key.
Test issue
After the test, if the battery voltage results too low, the battery LED becomes blinking.
Check the quality of the battery and if necessary, replace it.
Commands available
+
EXIT
to quit the submenu
5.22.4
OUTDOOR SIREN AND BATTERY TEST
On initiation of the test, the control panel reduces power supply voltage to 10.5V in
order to provoke the intervention of the battery.
The outdoor sirens are activated while they are powered by battery.
The test takes 60 seconds and can be interrupted at any time by pressing the EXIT
key.
Test issue
After the test, if the battery voltage results too low, the battery LED becomes blinking.
Check the quality of the battery and if necessary, replace it.
Commands available
+
EXIT
to quit the submenu
Radio
7
Con. consoles
Con. consoles
Waiting
T1 T2 T3 T4
Yes Yes --- ---
Test
2
Zones
Zones
- - -
Zones
Zone 025
Zones
Zone 026
Test
3
Indoor sirens
Test
4
Outdoor sirens
WARNING
During the test, the wireless indoor sirens work according to programming (see § 5.4), i.e. not active,
sounding, flashing, sflashing.
The sounding or flashing time, however, is irrelevant.
WARNING
During the test, the wireless outdoor sirens work according to programming (see § 5.4), i.e. not
active, sounding, flashing, sflashing.
The sounding or flashing time, however, is irrelevant.
Summary of Contents for TP16-256
Page 4: ...IV Installer Manual TP16 256...
Page 12: ...Index Installer Manual TP16 256 8...
Page 16: ...General Features Installer Manual TP16 256 1 4...
Page 18: ...Hardware Installer Manual TP16 256 2 2...
Page 30: ...Hardware Installer Manual TP16 256 2 14...
Page 46: ...Hardware Input Expansion Modules Installer Manual TP16 256 2A 16...
Page 50: ...Hardware Console Installer Manual TP16 256 2B 4...
Page 59: ...TP16 256 Installer Manual Output Expansion Modules Hardware 2D 5 ADDRESSES 6 TO 13...
Page 68: ...Hardware Programming Interfaces Installer Manual TP16 256 2E 6...
Page 70: ...Hardware Telephone Communicator with GSM Module Installer Manual TP16 256 2F 2...
Page 80: ...Hardware Wireless Expansion Modules Installer Manual TP16 256 2G 10...
Page 86: ...Set up Installer Manual TP16 256 3 6...
Page 91: ...TP16 256 Installer Manual Set up 3 11...
Page 184: ...Control by Console Installer Manual TP16 256 6 4 OPERATIONS WITHOUT CODE...
Page 196: ...Control by Console Installer Manual TP16 256 6 16...
Page 224: ...Technical Specifications Installer Manual TP16 256 8 14...
Page 226: ...Appendix A Transmission Protocols Installer Manual TP16 256 A 2...
Page 230: ...Appendix B Special Procedures Installer Manual TP16 256 B 2...
Page 242: ...Appendix B Special Procedures Installer Manual TP16 256 B 14...
Page 244: ...Appendix C Code Management Installer Manual TP16 256 C 2...
Page 247: ...TP16 256 Installer Manual Code Management Appendix C C 5...