Appendix F Comparisons 181
Comparisons
Service Clearances
LSM (door opening)
86.36 cm (34 in.)
Front
66 cm (26 in.)
LCU
39.0 cm (15.4 in.)
Rear
85 cm (33.5 in.)
LMU 81.3
cm
(32.0
in.)
Pass-thru ports
15.25 cm (6 in.)
9741e Drive Cabinet
81.3 cm (32.0 in.)
Door width
10.16 cm (4 in.)
Planning Requirements
Raised Floor Loading
244-293 kg/m
2
(50-60 lb/ft
2
)
Raised Floor Loading
260 kg/m
2
(120 lb/ft
2
)
Loading per pad
454 kg (1,000 lb)
Loading per pad
454 kg (1,000 lb)
Distribution pads
18 (per library)
Distribution pads
26 (with 3 expansions)
Assembly area
35 m
2
(400 ft
2
)
Assembly area
56 m
2
(600 ft
2
)
Power Requirements
Voltage (selectable)
200 to 240 VAC
Voltage
200 to 240 VAC
Frequency
47 to 63 Hz
Frequency
47 to 63 Hz
Phases (Current)
Single
Phases (Current)
Single Phase
Three Phase:
(
recommended
)
3 inputs
(24 Amps)
6 redundant
Delta (40 Amps)
Wye (24 Amps)
SUVA (24 Amps)
LCU/LSM
LMU
12 Amps
8 Amps
9741e Drive Cabinet
20 Amps
Power Consumption
LCU/LSM
LMU
9741e Drive Cabinet
1.5 kW
0.126 kW
1.47 kW
Power Consumption
(maximum loading**)
13.0 kW
Heat Output
LCU/LSM
LMU
9741e Drive Cabinet
3,750 Btu/hr
2,050 Btu/hr
8,047 Btu/hr
Heat Output
(maximum loading**)
44,380 Btu/hr
** Maximum loading = 64 tape drives, 4 fully
loaded racks, 8 HandBots, all front frame
components, plus redundant control modules
Minimum system
(16 drives)
3.56 kW
12,140 Btu/hr
Minimum system
(16 drives)
3.32 kW
11,320 Btu/hr
Maximum system
(60 drives, 3 x 9741E)
10.76 kW
36,700 Btu/hr
Maximum system
(64 drives, plus
8 HandBots, 4 racks)
12.27 kW
41,840 Btu/hr
Table 90. Comparisons Between PowderHorn and the SL8500 Library (Continued)
9310 PowderHorn
SL8500
Summary of Contents for StorageTek StreamLine SL8500
Page 4: ...Summary of Changes iv SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 12: ...Contents xii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 18: ...Tables xviii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 76: ...Introduction 56 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 97: ...E24254 01 Chapter 3 Site Survey Forms 77 Site Survey Forms Figure 21 Content Management Plan ...
Page 137: ...E24254 01 Chapter 4 Site Preparation 117 Site Preparation ...
Page 138: ...Site Preparation 118 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 198: ...Electrical Conversions 176 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 206: ...Comparisons 184 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 233: ...E24254 01 Appendix H Partitioning 211 Partitioning Make copies as necessary ...
Page 240: ...Partitioning 218 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 251: ...E24254 01 Appendix J Work Sheets 229 Work Sheets Figure 73 Content Management Work Sheet ...
Page 276: ...Index 254 SL8500 Systems Assurance Guide June 2011 E24254 01 ...
Page 277: ......
Page 278: ...Oracle Corporation Worldwide Headquarters 500 Oracle Parkway Redwood Shores CA 94065 U S A ...