Site Preparation
98 SL8500: Systems Assurance Guide • July 2011
E24254-01
Height Adjustments
Figure 33
shows the minimum and maximum library height specifications:
•
Minimum height = 231.4 cm (91 in.)
•
Maximum height = 236.6 cm (93.15 in.)
On a level floor, the first module’s height, between the module and floor,
should be adjusted to 25.4 mm ± 0.8 mm (1 in. ± 0.0325 in.).
The absolute minimum module-to-floor height permitted is 19 mm (0.75 in.).
Following these guidelines allows you to adjust the library to meet the
“Co-planar Requirements” on page 93
.
Clearances
Table 48
lists the clearances—library to ceiling—required to install side
covers, front and rear doors, and the upper modules.
To calculate maximum height and installation clearances, use the library
height range and add the overhead clearance.
Figure 33. Minimum and Maximum Height Specifications
1.
Customer
floor
2.
Adjustment range between floor and library:
-
minimum = 1.9 cm (0.75 in.)
-
maximum = 4.7 cm (1.85 in.)
3.
Bottom of the library
module floor
Table 48. Overhead Clearances
Overhead Clearance
Description
1.9 cm (0.75 in.)
Side cover installation
1.3 cm (0.5 in.)
Upper robotics interface module installation
2.5 cm (1 in.)
Facade installation
Hanging the front and rear doors on the hinges
Upper drive and electronics module installation
4.5 cm (1.75 in.)
Customer interface module roof installation
Storage expansion module roof installation
Summary of Contents for StorageTek StreamLine SL8500
Page 4: ...Summary of Changes iv SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 12: ...Contents xii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 18: ...Tables xviii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 76: ...Introduction 56 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 97: ...E24254 01 Chapter 3 Site Survey Forms 77 Site Survey Forms Figure 21 Content Management Plan ...
Page 137: ...E24254 01 Chapter 4 Site Preparation 117 Site Preparation ...
Page 138: ...Site Preparation 118 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 198: ...Electrical Conversions 176 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 206: ...Comparisons 184 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 233: ...E24254 01 Appendix H Partitioning 211 Partitioning Make copies as necessary ...
Page 240: ...Partitioning 218 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 251: ...E24254 01 Appendix J Work Sheets 229 Work Sheets Figure 73 Content Management Work Sheet ...
Page 276: ...Index 254 SL8500 Systems Assurance Guide June 2011 E24254 01 ...
Page 277: ......
Page 278: ...Oracle Corporation Worldwide Headquarters 500 Oracle Parkway Redwood Shores CA 94065 U S A ...