Site Preparation
86 SL8500: Systems Assurance Guide • July 2011
E24254-01
Air Flow Requirements
The air flow required to cool the SL8500 depends on the total number of
components installed within it, such as tape drives, load sharing DC power
supplies, and accessory racks.
Each of these components contribute to the total airflow required.
Calculations (requirements) for these individual components—using standard
air conditions at sea level (pressure) and 22
°C
/ 72
°F
(temperature)—are:
A maximum configured library with 64 tape drives, 24 DC power supplies, four
rack modules, and the electronic control module would require:
112.0m
3
/min. (3956 ft
3
/min.) of supply air to avoid recirculation.
Most configurations are smaller than this and require less air flow.
An example of a smaller configuration is 12 tape drives split between drive
bays for redundancy, one robot on each level, one rack module, and the
electronic control module.
This would require 33.30m
3
/min. (1176 ft
3
/min.).
The layout of the data center should account for the cooling requirements of
SL8500 as well as other equipment in the center—possibly through the
concept of having a cool aisle and hot aisle in accordance with environmental
best practices and controls.
Seismic or Earthquake Ratings
The requirements for seismic compatibility vary dramatically throughout the
world. As such, a standard “seismic” feature for the SL8500 modular library
system is not offered.
It is recommended that any customer who has seismic concerns work with
local experts who are familiar with the local code and requirements.
Professional Services can also be engaged to help coordinate this activity.
Table 42. Air Flow Requirements
Component
Measurement
Quantity
Tape drive
0.57m
3
/min. (20 ft
3
/min.) each
64 possible
DC power supply
0.71m
3
/min. (25 ft
3
/min.) each
24 possible
Rack Modules
13.59m
3
/min. (480 ft
3
/min.) each
4 possible
Electronics Module
4.42m
3
/min. (156ft
3
/min.)
Summary of Contents for StorageTek StreamLine SL8500
Page 4: ...Summary of Changes iv SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 12: ...Contents xii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 18: ...Tables xviii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 76: ...Introduction 56 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 97: ...E24254 01 Chapter 3 Site Survey Forms 77 Site Survey Forms Figure 21 Content Management Plan ...
Page 137: ...E24254 01 Chapter 4 Site Preparation 117 Site Preparation ...
Page 138: ...Site Preparation 118 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 198: ...Electrical Conversions 176 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 206: ...Comparisons 184 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 233: ...E24254 01 Appendix H Partitioning 211 Partitioning Make copies as necessary ...
Page 240: ...Partitioning 218 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Page 251: ...E24254 01 Appendix J Work Sheets 229 Work Sheets Figure 73 Content Management Work Sheet ...
Page 276: ...Index 254 SL8500 Systems Assurance Guide June 2011 E24254 01 ...
Page 277: ......
Page 278: ...Oracle Corporation Worldwide Headquarters 500 Oracle Parkway Redwood Shores CA 94065 U S A ...