User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
3.
TECHNICAL DATA
Power supply voltage
(depending on version)
External Fuse (required)
Power consumption
85...
230
...260V AC/DC; 50 ÷ 60 Hz
or 19...
24
...50V DC; 16V...
24
...35V AC
T - type, max. 2 A
typically 15 VA; max. 20 VA
Display (depending on version)
3.5” or 5.7”, TFT color graphic display, 320 x 240
pixels, with LED backlight
Sensor power supply output
24V DC ± 5% / max. 200 mA,
Basic communication interfaces
RS 485, 8N1/2, Modbus RTU, 1200 bit/s ÷ 115200 bit/s
USB Host port, USB Device port
Digital i
nput
1 input 0/15..24V DC,
galvanic isolation (low state:
0÷1V, high state:8÷24V)
power consumption
: 7,5 mA / 24V,
isolation: 1min @ 500V DC.
Optional communication module*
Second USB Host port
Serial RS-485 and RS-485/RS-232
Ethernet 10 Mb/sec. RJ-45
Optional input modules*
4/8/16/24x Voltage (0÷10V) / Current (0÷20mA)**
16/24x NTC (0÷100k)/ Voltage (0÷10V)/
Current (0÷20mA)/ Digital (TTL,HTL)**
6x Isolated current (4÷20mA),
4/6x RTD (Pt100, Pt500, Pt1000, Cu50, Cu100)**
4/8x/12 TC (J, K, S, T, N, R, E, L(GOST), B, C**
8/16/24x Digital input**
3/5x Universal input**
2/4x Universal counter input**
2/4x Hourmeter module**
2/4x Flo 2/4x Current input**
2/4x Pulse input + 2/4x Current input**
Optional output modules*
4/6x Relay 5A/250V
(cos
j
= 1)
**
8/12x Relay 1A/250V
(cos
j
= 1)
**
8/16/24x SSR driver (10
÷
15V, up to 100mA per
output)**
2/4/6/8x IO Passive current output (4
÷20mA)**
Protection level
IP 65 (device front side), optional IP 65 version
including gasket for panel cut-out sealing or
IP54 transparent door with key,
IP 40 (front USB version)
Housing type
Housing material
panel
NORYL - GFN2S E1
Housing dimensions
96 x 96 x 100 mm (small housing – 3.5” Display)
or 144 x 144 x 100 mm (big housing – 5.7” Display)
Mounting hole
90.5 x 90.5 mm (small housing – 3.5” Display)
or 137 x 137 mm (big housing – 5.7” Display)
9