User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
•
high level
– flip-flop triggers when the parameter channel selected in the
Clock source
is in the high logical state,
•
low level
– flip-flop triggers when the parameter channel selected in the
Clock source
is in the low logical state,
•
rising edge
– flip-flop triggers when the rising edge occurs in the parameter
channel selected in the
Clock source
,
•
falling edge
– flip-flop triggers when the falling edge occurs in the parameter
channel selected in the
Clock source
,
–
R input mode
– available for
Function=flip flop
, the user can set the following
options:
•
disabled
– resetting flip-flop R input in inactive,
•
from log. channel
– means that the flip-flop R input source will be the logical
state of the selected logical channel,
•
from channel (negation)
– means that the flip-flop R input source will be
the negated logical state of the selected logical channel,
–
R input source
– available for
Function=flip flop
, selects a logical channel which
will be the flip-flop R input source,
–
S input mode
– available for
Function=flip flop
, the user can set the following
options:
•
disabled
– setting flip-flop S input in inactive,
•
from log. channel
– means that the flip-flop S input source will be the logical
state of the selected logical channel,
•
from channel (negation)
– means that the flip-flop S input source will be
the negated logical state of the selected logical channel,
–
S input source
– available for
Function=flip flop
, selects a logical channel which
will be the flip-flop S input source,
–
Type of source Y
- available for certain math functions. Available types are:
•
channel
- meaning that the
'Y'
source will be a logical channel selected from
the list in the
Source Y
parameter,
•
value
- means that the
'Y'
source will be a constant value entered in the
Source Y
parameter,
–
Source Y
- available for certain math functions. Depends on the
Type of source Y
parameter. This parameter allows the user to:
•
select a logical channel from the list (
Type of source Y=channel
),
•
or enter the Set point value (
Type of source Y=value
),
–
Unit
- available for certain trigonometric functions. Allows an option to be selected:
•
degree
•
radian
108