User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
•
in
Output value
parameter in the
Point 1
section write
0°C
,
•
in
Input value
parameter in the
Point 2
section write
20
,
•
in
Output value
parameter in the
Point 2
section write
20°C
,
–
for
Display
block parameters:
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0.0
,
•
in
Graph low
write
10°C
,
•
in
Graph high
write
50°C
,
–
using the arrows in the top navigation bar, select any
Logical channel
such as 2,
–
in the
Name
parameter write
Temperature 2
,
–
Mode
parameter set as
Modbus
,
–
Port
parameter set as
MB1 (MASTER)
,
–
SLAVE device
parameter set as
Addr.8:“Temp. converter”
,
–
Device
input
parameter set as
Inp.2:HR 1h,b0-15
that reads
Register 1h
from
SLAVE 2
device,
–
all the other parameters should be set like in the previously configured logical
channel,
In the next step you need to define a
Group
to set up logical channels to view them in
one window on the screen. To do this:
–
enter the
Group
menu to enable the
Group 1
if it is off,
–
in the
Name
parameter write
Temperature
,
–
for
Channels
block parameters:
•
Slot 1
parameter set as
logical channel 1
called the
Temperature 1
,
•
Slot 2
parameter set as
logical channel 2
called the
Temperature 2
,
•
other parameters in this block –
Slot 3÷6
, set as
disabled
, because we want to
show only two logical channels,
–
all the other parameters should be on default settings,
The last step is to define the
Initial view
displayed on the LCD screen when the device
starts. The initial View has to display a defined Group of logical channels: 1, 2 in the values
mode. To do this:
–
enter the
General settings
menu,
–
for
Initial view
block parameters,
•
Display
mode
parameter set as
values
,
•
Displayed group
parameter set as
Group 1: Temperature
,
After the whole configuration exit the menu by pressing
Save changes
, the result will be
visible as soon as the first measurement is done.
137