User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
•
Format
parameter set as
numeric
,
•
Precision
parameter set as
0
,
•
in
Graph low
parameter write
-200°C
,
•
in
Graph high
parameter write
1370°C
,
b) For the temperature reading of sensor 2 with the symbol A2:
–
Using the arrows in the top navigation bar, select any
Logical channel
(except for 1)
for example 2,
–
in the
Name
parameter write
Temperature A2
,
–
Mode
parameter set as
hardware input
,
–
Source
parameter set as
Source
-
Inp. A2: Thermocouple
–
Other parameters are set as the sensor 1.
c) For the temperature reading of sensor 3 with the symbol A3:
–
Using the arrows in the top navigation bar, select any
Logical channel
(except for 1
and 2) for example 3,
–
in the
Name
parameter write
Temperature A3
,
–
Mode parameter set as
hardware input
,
–
Source parameter set as
Source
-
Inp. A3: Thermocouple
–
Other parameters are set as the sensor 1.
d) For the temperature reading of sensor 4 with the symbol A4:
–
Using the arrows in the top navigation bar, select any
Logical channel
(except for 1,
2 and 3) for example 4,
–
in the
Name
parameter write
Temperature A4
,
–
Mode parameter set as
hardware input
,
–
Source parameter set as
Source
-
Inp. A4: Thermocouple
–
Other parameters are set as the sensor 1.
e) For the alarm state,
–
using the arrows in the top navigation bar, select any
Logical channel
(except for 1,
2, 3 and 4) e.g. 5,
–
in the
Name
parameter write
Alarm
,
–
Mode parameter set as
Math function
,
–
enter the
Function
submenu to select the appropriate function that allows to
calculate the alarm condition,
•
Function
parameter set as
All X[i] > Y
,
•
in
Source X
parameter select logical channels 1, 2, 3, 4 which we defined as a
measure of temperature,
•
X error handling
parameter set as
errors forwarded to result
,
•
Type of source Y
parameter set as
value
,
•
in
Source Y
parameter write
140
,
–
for
Displaying
block parameters:
•
Format parameter set as
binary
,
•
in
Off-state text
write
LO
with blue font color,
•
in On-state text write
HI
with red font color,
•
in
Graph low
write
0
,
•
in
Graph high
write
1
,
–
exit the
Logical channels
menu,
129