User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
To read the output value from the module:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Logical channels
menu,
–
using the arrows in the top navigation bar, select any
Logical channel
such as 5,
–
in the
Name
parameter write
Relay 1
,
–
Mode
parameter set as
Hardware output monitor
,
–
Source
parameter set as
Out. C1: Relay
(see the connection in
–
for
Displaying
block parameters:
•
Format
parameter set as
binary
,
•
in
Off-state text
write
OFF
with red font and yellow background,
•
in
On-state text
write
HI
with green font and violet background,
•
in
Graph low
write
0
,
•
in
Graph high
write
1
,
In the next step you need to define a
Group
to set up logical channels to view them in
one window on the screen. To do this:
–
enter the
Group
menu to enable the
Group 1
if it is off,
–
in the
Name
parameter write
Monitor output
,
–
for
Channels
block parameters,
•
Slot 1
parameter set as
Logical channel 5
called
Relay 1
,
•
other parameters in this block -
Slot 2÷6
, set as
disabled
, because we want to
show only one logical channel,
The last step is to define the
Initial view
displayed on the LCD screen when the device
starts. The initial View has to display the defined Group 1 in the values mode. To do this:
–
enter the
General settings
menu,
–
for
Initial view
block parameters:
•
Display
mode
parameter set as
value
,
•
Displayed group
parameter set as
Group 1: Output monitor
,
After the whole configuration exit the menu by pressing
Save changes
, the result will be
visible as soon as the first measurement is done. The window view of MultiCon with the above
configuration is shown in
Fig. 7.74. The proposition of Example 4 result
135