User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
type
range
temperature
range
resolution
accuracy
accuracy
[ Ω ]
[ °C ]
[ Ω ]
[ °C ]
[ % ]
Pt100
0÷325
-100÷600
0.01
±1
±0.14
Pt500
0÷3250
-100÷600
0.1
±2
±0.3
Pt1000
0÷3250
-100÷600
0.1
±1
±0.14
Pt'50
0÷325
-200÷600
0.01
±2
±0.25
Pt'100
0÷325
-200÷600
0.01
±1
±0.12
Pt'500
0÷3250
-200÷600
0.1
±2
±0.25
Cu50
0÷325
-50÷200
0.01
±1.8
±0.73
Cu100
0÷325
-50÷200
0.01
±0,9
±0.37
Cu'50
0÷325
-200÷200
0.01
±1.6
±0.4
Cu'100
0÷325
-200÷200
0.01
±0.8
±0.2
Ni100
0÷325
-60÷180
0.01
±0.7
±0.3
Ni500
0÷3250
-60÷180
0.1
±1.4
±0.58
Ni1000
0÷3250
-60÷180
0.1
±0.7
±0.3
Tab. 8.16 RTD measurement accuracy for the UN3 and UN5 modules
type
norm
Pt100
PN-EN 60751:2009
Pt500
PN-EN 60751:2009
Pt1000
PN-EN 60751:2009
Pt'50
GOST 6651-94 (W
100
=1.3916)
Pt'100
GOST 6651-94 (W
100
=1.3916)
Pt'500
GOST 6651-94 (W
100
=1.3916)
Cu50
GOST 6651-94 (W
100
=1.3916)
Cu100
GOST 6651-94 (W
100
=1.3916)
Cu'50
PN-83M-53852 (W
100
=1.4280)
Cu'100
PN-83M-53852 (W
100
=1.4280)
Ni100
PN-EN 60751:2009
Ni500
PN-EN 60751:2009
Ni1000
PN-EN 60751:2009
Tab. 8.17 RTD norm for the UN3 and UN5 modules
289