User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
returns
Err
,
Hi
or
Lo
value. This parameter has the following options:
•
no change
- means that at the time of an alarm state there is no change on the
output,
•
immed. OFF
- means that in times of an alarm state the device immediately
switches the output to low state,
•
immed. ON
- means that in times of an alarm state the device immediately
switches the output to high state,
•
timed OFF
- means that in times of an alarm state the device switches the
output to low state after a time delay set in the
Timing
parameter block,
•
timed ON
- means that in times of an alarm state the device switches the output
to low state after a time delay set in the
Timing
parameter block,
–
Levels
block parameter - these parameters allow the user to set the range of
changes of the output depending on the input signal, discussed below in this
Chapter
,
–
Timing
parameter block - these parameters allow the user to set the delay time
change the output state and minimum duration of the output state, discussed below
in this
Chapter
,
Levels
These parameters depend on the
Mode
parameter. The options are:
–
Level
- this parameter defines the source signal level at which the output switches
the state (from low to high state or from high to low state), occurs for the mode:
•
above level
- above the level we get a high state at the output,
•
below level
- below the level we get a high state at the output,
–
Lower level and Upper level
- these parameters define the range at which a switch
the output state (from low to high state or vice versa from high to low state), occurs
for the mode:
•
inside range
- if the input data is within the defined range at the output we get
a high state,
•
outside range
- if the input data is outside the defined range at the output we
get a high state,
–
Hysteresis
– this parameter defines the offset for a switch state on the output,
Timing
The parameters of this block include:
–
ON delay
– it is the time that must pass from the time of a switch request to
the actual switch from low state to high state (see
–
OFF delay
- it is the time that must pass from the time of a switch request to
the actual switch from high state to low state (see
–
Min.ON time
- the minimum duration of a high state (if the output switches to high
state the low state will occur not faster than
Minimum ON time
–
Min.OFF time
- the minimum duration of a low state (if the output switches to low
state the high state will occur not faster than
Minimum OFF time
Note!
If the external output is active (see the parameter
Output active=yes
in the
Chapter 7.15.3.2. Modbus MASTER - Device channels parameter block
) for
Mode=disabled
the device sends the '0' value to a Slave device.
7.11.3.
External outputs - Control type: as a linear output
180