User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Fig. 7.117.
Responses of the iner
tial block
depending on factor
T
–
Controller running modes
parameter block – this block contains the following
parameters:
•
Mode
– defines when the controller will turn on:
◦
ON
– always turned on,
◦
OFF
– always turned off,
◦
from log. channel
– turned on depending on the logical channel,
•
Source –
defines logical channel, that will be a source of run, only visible for
Mode: from log. channel
,
•
Triggering
– defines the event triggering the controller work, there are the
following options:
◦
high level
– triggering of start occurs when triggering channel is in high
level,
◦
low level
– triggering of start occurs when triggering channel is in low level,
◦
rising edge
– triggering of start occurs when triggering channel is rising
edge,
◦
falling edge
– triggering of start occurs when triggering channel is falling
edge,
–
Fuzzy Logic parameters
parameter block - this block has the following parameters:
•
Mode
– turn on the additional fuzzy logic block to the controller, available
options are:
◦
ON
– always turned on,
◦
OFF
– always turned off,
•
Slew rate
202
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
2
0
2
4
6
8
10
12
14
hard
medium
soft
time
In
er
tia
l b
lo
ck
r
es
po
ns
e