User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Fig. 7.155. Connection diagram for the Modbus MB2 port
16-bits Slave device registers description is shown in
Register
Range
Register description
01h
0÷0x0FFFFh
Set point value (younger word of 32-bits float value)
02h
0÷0x0FFFFh
Set point value (older word of 32-bits float value)
04h
0÷1
Valve position: 0-closed, 1-open,
08h
0÷1
Alarm state: 0-off, 1-on,
Tab. 7.12 Description of 16-bits Slave device registers
In the first step:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Modbus
menu,
–
using the arrows in the upper right corner choose
Port number
:
1
(
MB1
in
–
Mode
parameter set as
MASTER
,
–
Baud rate
parameter set as
19200 bits/sec.
(it should be the same as in the SLAVE
device),
–
Format
parameter set as
8N1
,
–
in
Request timeout
parameter write
0.2 sec.
,
–
in
Request retrials
parameter write
3
,
–
press the
Slave devices
button:
•
using the arrows in the upper right corner select
Modbus address
of the Slave
device, in this case:
5
,
•
Device type
parameter set as
defined
,
•
in the
Device name
parameter write
Flowmeter
,
•
in the
Device channels
parameter block press the
Output list
button to define
the register to write,
252
19
16
17
18
14
15
RJ-45
ETH
USB host
RS
-4
85
(2
)
RxD
A+
B-
13
10
11
12
9
A+
B-
GND
TxD
CTS
RTS
R
S
-2
32
+
R
S
-4
85
(3
)
19
Slot D - ACM Module
MB2 port
GND
B-
A+
GND
GND
Power supply
(depending on version)
1
2
8
5
6
7
3
4
SERVICE
+24V DC ±5%
(
I
max. = 200mA)
digital input
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
Slave device 1
Slave address: 5
Register: 1h
Register: 2h
Register: 4h
Baud rate: 19200 bit./sec.
Device name:Flowmeter
Registers:
Modbus settings:
Register: 8h