User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
RT4
RT6
Resistance measurement
precision
0.1% @ 25˚C
0.1% @ 25˚C
Temperature stability
50 ppm/˚C
50 ppm/˚C
Connection method
2, 3 and 4 wire
(switched manually)
2, 3 and 4 wire
(switched manually)
Input impedance
4
k
W
4
k
W
Measurement wires resistance
max. 20Ω (every wire)
max. 20Ω (every wire)
Sampling period
1s
1s
Weight
72 g
62 g
Due to the real measurement accuracy it is recommended to set the temperature display
accurate to one decimal place.
producer's
website
Tab. 8.10 Technical data for the RT4 and RT6 modules
type
range
temperature
range
resolution
accuracy
accuracy
[ Ω ]
[ °C ]
[ Ω ]
[ °C ]
[ % ]
Pt100
0÷325
-100÷600
0.01
±1
±0.14
Pt500
0÷3250
-100÷600
0.1
±2
±0.3
Pt1000
0÷3250
-100÷600
0.1
±1
±0.14
Pt'50
0÷325
-200÷600
0.01
±2
±0.25
Pt'100
0÷325
-200÷600
0.01
±1
±0.12
Pt'500
0÷3250
-200÷600
0,1
±2
±0.25
Cu50
0÷325
-50÷200
0.01
±1.8
±0.73
Cu100
0÷325
-50÷200
0.01
±0.9
±0.37
Cu'50
0÷325
-200÷200
0.01
±1.6
±0.4
Cu'100
0÷325
-200÷200
0.01
±0.8
±0.2
Ni100
0÷325
-60÷180
0.01
±0.7
±0.3
Ni500
0÷3250
-60÷180
0.1
±1.4
±0.58
Ni1000
0÷3250
-60÷180
0.1
±0.7
±0.3
Tab. 8.11 Measurement accuracy for the RT4 and RT6 modules
283