User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
A detailed description of the modes is presented in the following chapters.The channel for
Mode=disabled
has only one parameter - the
name
of the channel. In other modes the
Logical channels
are
active
and may affect the processing and control data.
The parameters and blocks of parameters common for
active Logical channels
:
–
Name
- it gives the name to the logical channel,
–
Unit
- is related with a data source of the channel,
•
for
Built-in modules
it will automatically use a default
Unit
,
•
for
Mode=Set point value
and
Mode=Controller
the
Unit
can be defined freely,
directly in the
Logical Channel
menu,
•
for other modes the
Unit
can be added only using the
Scaling
parameter (see
below in this
Chapter
for discussion about the
Scaling
parameter),
–
Mode
- in this parameter the user selects the source of the data for the logical
channel. It is possible to select one of ten modes:
•
disabled
,
•
Hardware input
•
Hardware output monitor
•
Modbus
•
Set point value
•
Math function
•
Controller
•
Profile / timer
•
Profile/timer (cycle counter)
•
Data from other channel
–
Latch
parameter block - allows the user to set the
latch function
which will hold the
last value of a channel; this block has the following parameters:
•
Mode
- this parameter allows the user to choose how to trigger the latch
function; there are 2 options:
◦
disabled
- the latch function is disabled,
◦
from logic channel
- the latch function is activated depending on the value
of the channel selected in the
Triggering source
parameter,
•
Triggering source
- this parameter is only visible if the user sets
Mode=from logic channel
; using this parameter the user chooses a logical
channel which is the triggering source of the latch function (when the value of
the triggering channel is
≤0
the latch is
active
, for the value
>0
the latch is
disabled
),
During the device restart, the logical channels, which have the latch function
enabled, are of the value: '
0
' and on the LCD screen blinking dashes '
----
' appear
in place of the value.
–
Processing
parameter block - is used for scaling and filtering data (for explanation
see below)
–
Displaying
parameter block - for these parameters the user selects the format and
range of the data displayed on the screen. For more information about
Displaying
parameters see below in this
Chapter
.
76