User Manual For - CONTROLLER/DATA RECORDER MultiCon CMC-99/141
Fig. 7.154. Connection diagram for the Modbus port MB1
Description of the SLAVE device register shown in
Register
Range
Register description
01h
-4000 ÷ +8500
The temperature measured with a resolution given to 2 decimal places
(in the U2 code, excluding decimal point, for example, the value of
3523 means the temperature of 35.23°C)
02h
00h, 10h,
20h,40h, 80h
Status of the temperature contains the error code which must be
interpreted as follows:
00h
-
measuring correctly
10h
- flooding the interior of the sensor
20h
- damage temperature sensor
40h
- measured temperature is lower -40°C
80h
- measured temperature is upper 85°C
03h
0÷2
Specify the decimal point as a result, the value of 2 means that a point
precedes the last 2 digits, the value of 0 means no decimal point
Tab. 7.11 Description of the SLAVE device registers
In the first step:
–
touch the screen and press the
Menu
button,
–
press the
Device configuration
button,
–
enter the
Modbus
menu,
–
using the arrows in the upper right corner choose
Port number
:
1
(
MB1
in
–
Mode
parameter set as
MASTER
,
–
Baud rate
parameter set as
9600 bits/sec.
(it should be the same as in the SLAVE
device),
–
Format
parameter set as
8N1
,
–
in
Request timeout
parameter write
0.2 sec.
,
–
in
Request retrials
parameter write
3
,
249
Power supply
(depending on version)
1
2
8
5
6
7
3
4
SERVICE
+24V DC ±5%
(
I
max. = 200mA)
digital input
0/15..24V DC
RS-485
GND
GND
A+
B-
isolated
Master
Device
Slave device 1
Slave address: 1
Register: 1h
Register: 2h
Register: 3h
Baud rate: 9600 bit./sec.
Device name:Temp. converter
Registers:
Modbus settings:
Slave device 2
Slave address: 8
Register: 1h
Register: 2h
Register: 3h
Baud rate: 9600 bit./sec.
Device name:Temp. converter
Modbus settings:
Registers:
GND
B-
A+
Port MB1