Diagnostics
11.2 List of faults and alarms
SINAMICS V90, SIMOTICS S-1FL6
408
Operating Instructions, 04/2019, A5E36037884-007
Alarm
Cause
Remedy
A52900: Failure during data
copying
•
Copying is halted.
•
The micro SD card/SD card was
plugged out.
•
The drive is not in the stop state.
•
Re-plug in the micro SD card/SD card.
•
Make sure the drive is in the stop state.
A52901: Braking resistor
reaches alarm threshold
The heat capacity reaches the threshold
(p29005) of the braking resistor capacity.
•
Change the external braking resistor.
•
Increase deceleration time.
A52902: Quick stop (EMGS)
missing
Implement servo on when the digital input
(EMGS) is switched off.
Switch on the digital input (EMGS) and then
implement servo on.
A52932: PTO max limit
For incremental encoder, when PTO fre-
quency exceeds 280K, drive will output
A52932 to remind that exceed limitation.
For absolute encoder, when PTO frequen-
cy exceeds 120K, drive will output A52932
to remind that exceed limitation.
Change PTO ratio.