Control functions
7.5 Internal position control (IPos)
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
245
The whole process is shown in the diagram below:
Follow the steps below to perform referencing with this mode:
1.
Set relevant parameters.
Parameter
Range
Default
Unit
Description
p2599
-2147482648 to
2147482647
0
LU
Sets the position value for the reference
point coordinate.
p2600
-2147482648 to
2147482647
0
LU
Reference point offset
p2604
0 to 1
0
-
Sets signal source for start direction of
searching:
•
0: start in positive direction
•
1: start in negative direction
p2608
1 to 40000000
300
1000
LU/mi
n
Speed for searching zero mark
p2609
0 to 2147482647
20000
LU
Maximum distance for searching the zero
mark
p2611
1 to 40000000
300
1000
LU/mi
n
Speed for searching reference point
2.
Configure the signal SREF.