Parameters
10.2 Parameter list
SINAMICS V90, SIMOTICS S-1FL6
366
Operating Instructions, 04/2019, A5E36037884-007
Par. No.
Name
Min
Max
Factory
Setting
Unit Data
type
Effective
Can be
changed
p29132
Gain switching condition:
Position setpoint frequen-
cy
0
214700006
4
100
100
0
LU/
min
Float
IM
T
Description: Triggers pulse input frequency (PTI) threshold or internal position speed (IPos) threshold for gain
switching. If the gain switching function is enabled and this condition is selected:
1.
PTI
–
Switch from the first group of control parameters to the second group when the pulse train input pulse
is higher than the threshold.
–
Switch from the second group of control parameters to the first group when the pulse train input is low-
er than the threshold.
2.
IPos
–
Switch from the first group of control parameters to the second group when the speed of fixed position
setpoint is larger than the threshold.
–
Switch from the second group of control parameters to the first group when the IPos is smaller than the
threshold.
p29133
Gain switching condition:
Actual speed
0
214700006
4
100
rpm Float
IM
T
Description: Triggers speed threshold for gain switching. If the gain switching function is enabled and this
condition is selected:
•
Switch from the first group of control parameters to the second group when the actual motor speed is
larger than the threshold.
•
Switch from the second group of control parameters to the first group when the actual motor speed is
smaller than the threshold.
p29139
Gain switching time con-
stant
8
1000
20
ms Float
IM
T
Description: Time constant for gain switching. Set this parameter to avoid frequent gain switches that reduces
system reliability.
p29140
PI to P: Mode selection
0
5
0
-
U16
IM
T
Description: Selects a condition for the switch from PI control to P control under the speed loop.
•
0: Disabled
•
1: Torque is higher than a parameterizable setting value.
•
2: Using the digital input signal (G-CHANGE).
•
3: Speed is higher than a parameterizable setting value.
•
4: Acceleration is higher than a parameterizable setting value.
•
5: Pulse deviation is higher than a parameterizable setting value.
Note: Only when the auto tuning function (p29021=0) and gain switching function are both disabled can the
PI/P switching function be used.
p29141
PI to P switching condi-
tion: Torque
0
300
200
%
Float
IM
T
Description: Triggers torque threshold for PI/P switching. If the PI/P switching function is enabled and this
condition is selected:
•
Switch from the PI control to the P control when the actual torque is larger than the threshold.
•
Switch from the P control to the PI control when the actual torque is smaller than the threshold.