13.8
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Testing and Troubleshooting
Relay Self-Tests
Relay Self-Tests
The relay runs a variety of self-tests. The relay takes the following corrective
actions for out-of-tolerance conditions (see
➤
Protection Disabled: The relay disables overcurrent elements
and trip/close logic. All output contacts are de-energized. The
EN
front-panel LED is extinguished.
➤
ALARM Output: The
ALARM
output contact signals an alarm
condition by going to its de-energized state. If the
ALARM
output
contact is a B contact (normally closed), it closes for an alarm
condition or if the relay is de-energized. If the
ALARM
output
contact is an A contact (normally open), it opens for an alarm
condition or if the relay is de-energized. Alarm condition
signaling can be a single five-second pulse (Pulsed) or
permanent (Latched).
➤
The relay generates automatic STATUS reports at the serial
port for warnings and failures.
➤
The relay displays failure messages on the relay LCD display
for failures.
Use the serial port
STATUS
command or front-panel
{STATUS}
pushbutton to
view relay self-test status.
Table 13.3
Relay Self Tests
(Sheet 1 of 2)
Self-Test
Condition
Limits
Protection
Disabled
ALARM
Output
Description
IA, IB, IC, IN,
VA, VB, VC,
VS
Offset
Warning
30 mV
No
Pulsed
Measures the dc offset at each of the input chan-
nels every 10 seconds.
Master Offset
Warning
20 mV
No
Pulsed
Measures the dc offset at the
A/D every 10 seconds.
Failure
30 mV
Yes
Latched
+5 V PS
Warning
+4.80 V
+5.20 V
No
Pulsed
Measures the +5 V power supply
every 10 seconds.
Failure
+4.65 V
+5.40 V
Yes
Latched
+5 V REG
Warning
±4.75 V
+5.20,
–5.25 V
No
Pulsed
Measures the regulated 5 V power supply
every 10 seconds.
Failure
±4.50 V
+5.40,
–5.50 V
Yes
Latched
+12 V PS
Warning
±11.50 V
±12.50 V
No
Pulsed
Measures the 12 V power supply
every 10 seconds.
Failure
±11.20 V
±14.00 V
Yes
Latched
+15 V PS
Warning
±14.40 V
±15.60 V
No
Pulsed
Measures the 15 V power supply
every 10 seconds.
Failure
±14.00 V
±16.00 V
Yes
Latched
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...