5.3
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Trip and Target Logic
Trip Logic
Set Trip
. All trip conditions:
➤
Communications-Assisted Trip
➤
Direct Transfer Trip
➤
Switch-Onto-Fault Trip
➤
Other Trips
are combined into OR-1 gate. The output of OR-1 gate asserts Relay Word bit
TRIP to logical 1, regardless of other trip logic conditions. It also is routed
into the Minimum Trip Duration Timer (setting TDURD).
As shown in the time line example in
, the Minimum Trip Duration
Timer (with setting TDURD) outputs a logical 1 for a time duration of
“TDURD” cycles any time it sees a rising edge on its input (logical 0 to
logical 1 transition), if it is not already timing (timer is reset). The TDURD
timer assures that the TRIP Relay Word bit remains asserted at logical 1 for a
minimum of “TDURD” cycles. If the output of OR-1 gate is logical 1 beyond
the TDURD time, Relay Word bit TRIP remains asserted at logical 1 for as
long as the output of OR-1 gate remains at logical 1, regardless of other trip
logic conditions.
The Minimum Trip Duration Timer can be set no less than 4 cycles.
Figure 5.2
Minimum Trip Duration Timer Operation
)
The OPEN Command Is No Longer Embedded in Trip Logic
In previous firmware versions of the SEL-351 Relay, the
OPEN
command
was embedded in the trip logic in
. The
OPEN
command was
routed directly into the Minimum Trip Duration Timer, along with the output
of logic gate OR-1.
The
OPEN
command is no longer directly embedded in the trip logic. This
change was made so that users can supervise the
OPEN
command if desired
via setting TR.
Example output of
OR-1 (input into
Minimum Trip
Duration Timer and
OR-2)
Resultant logic
output of Minimum
Trip Duration Timer
(input into OR-2)
OR-combination of
above two logic
traces (inputs into
OR-2 to drive Relay
Word bit TRIP)
Rising-edge
input occurring
when the
Minimum
Trip Duration
Timer is reset
TDURD
TDURD
TDURD
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...