12.5
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Standard 15/30-Cycle Event Reports
The event type designations
AG
through
CAG
are only entered in
the
Event:
field if the fault locator operates successfully. If the fault locator
does not operate successfully, just TRIP or ER is displayed.
Fault Location
The relay reports the fault location if the EFLOC setting = Y and the fault
locator operates successfully after an event report is generated. If the fault
locator does not operate successfully,
$$$$$$
is listed in the field. If EFLOC =
N, the field is blank. Fault location is based upon the following:
➤
line impedance settings Z1MAG, Z1ANG, Z0MAG, and
Z0ANG
➤
source impedance settings Z0SMAG and Z0ANG
➤
corresponding line length setting LL
See the
SET
command in
and corresponding
Settings Explanations on page 9.37) on page SET.1
for information on the line
parameter settings.
Targets
The relay reports the targets at the rising edge of TRIP. The targets include:
INST
,
COMM
,
S0TF
,
50
,
51
, and
81
. If there is no rising edge of TRIP in the
report, the
Targets
field is blank. See
Front-Panel Target LEDs on page 5.31
Currents
The
Currents (A pri), ABCNGQ:
field shows the currents present in the event
report row containing the maximum phase current. The listed currents are:
➤
Phase (A = channel IA, B = channel IB, C = channel IC)
➤
Neutral ground (N = channel IN)
Table 12.1
Event Types
Event Type
Description
AG, BG, CG
Single phase-to-ground faults. Appends T if TRIP asserted.
A, B, C
Single phase-to-ground faults (Petersen Coil-
and ungrounded/ high-impedance grounded systems only).
Appends T if TRIP asserted.
ABC
Three-phase faults. Appends T if TRIP asserted.
AB, BC, CA
Phase-to-phase faults. Appends T if TRIP asserted.
ABG, BCG, CAG
Phase-to-phase-to-ground faults. Appends T if TRIP asserted.
TRIP
Assertion of Relay Word bit TRIP (fault locator
could not operate successfully to determine the
phase involvement, so just TRIP is displayed).
ER
SEL
OGIC
control equation setting ER.
Phase involvement is indeterminate.
TRIG
Execution of
TRIGGER
command.
PULSE
Execution of
PULSE
command.
NOTE:
The fault locator will not
operate properly unless three-phase
voltages are connected.
NOTE:
The fault locator is most
accurate when the fault currents last
longer than two cycles.
NOTE:
The fault locator will not
operate for phase-to-ground faults on
Petersen Coil- or ungrounded/high-
impedance grounded systems.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...