10.33
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Serial Port Communications and Commands
Command Explanations
Command
TAR SH1 10
is executed in the following example:
=>
TAR SH1 10 <Enter>
79RS 79CY 79LO SH0 SH1 SH2 SH3 SH4
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
79RS 79CY 79LO SH0 SH1 SH2 SH3 SH4
0 0 1 0 1 0 0 0
0 0 1 0 1 0 0 0
=>
Note that Relay Word row containing the SH1 bit is repeated 10 times. In this
example, the reclosing relay is in the Lockout State (79LO = logical 1), and
the shot is at shot = 1 (SH1 = logical 1). Command
TAR 35
will report the
same data since the SH1 bit is in Row 35 of the Relay Word.
Command
TAR ROW LIST
is executed in the following example
(SEL-351-6 with 0.2 A nominal neutral channel):
=>
TAR ROW LIST <Enter>
Row EN TRIP INST COMM SOTF 50 51 81
0 1 1 0 0 0 0 1 0
Row A B C G N RS CY LO
1 1 1 1 0 0 0 0 1
Row 50A1 50B1 50C1 50A2 50B2 50C2 50A3 50B3
2 0 0 0 0 0 0 0 0
Row 50C3 50A4 50B4 50C4 50AB1 50BC1 50CA1 50AB2
3 0 0 0 0 0 0 0 0
Row 50BC2 50CA2 50AB3 50BC3 50CA3 50AB4 50BC4 50CA4
4 0 0 0 0 0 0 0 0
.
. (54 rows not shown)
.
Row 27AB2 27BC2 27CA2 59AB2 59BC2 59CA2 59Q2 3V0
59 0 0 0 0 0 0 0 1
Row V1GOOD * * V0GAIN INMET ICMET IBMET IAMET
60 0 0 0 1 1 1 1 1
Row GNDSW 50NF 50NR 32NE F32N R32N 32NF 32NR
61 1 0 0 0 0 0 0 0
Row PMDOK F32W R32W F32C R32C NSA NSB NSC
62 0 0 0 0 0 0 0 0
=>
TIM Command (View/Change Time)
TIM
displays the relay clock. To set the clock, type
TIM
and the desired
setting, then press
<Enter>
. Separate the hours, minutes, and seconds with
colons, semicolons, spaces, commas, or slashes. To set the clock to 23:30:00,
enter:
Table 10.7
SEL-351 Relay Word and Its Correspondence to TAR Command
TAR 0 (Front-
Panel LEDs)
EN
TRIP
INST
COMM
SOTF
50
51
81
TAR 1 (Front-
Panel LEDs)
A
B
C
G
N
RS
CY
LO
NOTE:
After setting the time, allow
at least 60 seconds before powering
down the relay or the new setting may
be lost.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...