12.9
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Standard 15/30-Cycle Event Reports
➤
Optoisolated input contact bounce on channels
IN101
–
IN106
➤
Transients on the station dc battery channel Vdc (power input
terminals
Z25
and
Z26
)
The filters for ac current and voltage and station battery are fixed. You can
adjust the optoisolated input debounce via debounce settings (see
).
Raw event reports display one extra cycle of data at the beginning of the
report.
Unfiltered Event Reports With PTCONN = DELTA
When global setting PTCONN = DELTA, the raw event report voltage
columns reflect the signals applied to relay terminals
VA-N
,
VB-N
,
VC-N
, even
though the relay is configured for an open-delta PT connection (see
). If the relay is properly wired, the value shown in column
VB
should be at or near 0 kV, because input terminal
VB
is tied to terminal
N
.
Column
VA
should reflect power system voltage V
AB
, and column
VC
should
reflect power system voltage V
CB
(or –V
BC
).
Clearing Standard
Event Report Buffer
The
HIS C
command clears the event summaries and corresponding standard
event reports from nonvolatile memory. See
for more information on the
HIS
(Event
Summaries/History) command.
Standard Event
Report Column
Definitions
Refer to the example event report in
to view event report columns.
This example event report displays rows of information each 1/4 cycle and
was retrieved with the
EVE
command.
The columns contain ac current, ac voltage, station dc battery voltage,
frequency, output, input, and protection and control element information.
Current, Voltage, and Frequency Columns
summarizes the event report current, voltage, and frequency
columns.
Table 12.2
Standard Event Report Current, Voltage, and Frequency Columns
(Sheet 1 of 2)
Column
Heading
Definition
IA
Current measured by channel IA (primary A)
IB
Current measured by channel IB (primary A)
IC
Current measured by channel IC (primary A)
IN
Current measured by channel IN (primary A)
IG
Calculated residual current IG = 3I
0
= IA + IB + IC (primary A)
VA
Voltage measured by channel VA (primary kV, PTCONN = WYE)
a
VB
Voltage measured by channel VB (primary kV, PTCONN = WYE)
VC
Voltage measured by channel VC (primary kV, PTCONN = WYE)
VAB
Power system phase-to-phase voltage V
AB
(primary kV, PTCONN = DELTA)
b
VBC
Power system phase-to-phase voltage V
BC
(primary kV, PTCONN = DELTA)
NOTE:
is on multiple
pages.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...