12.2
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Standard 15/30-Cycle Event Reports
Standard 15/30-Cycle Event Reports
See
for an example event report
Event Report Length
(Settings LER and
PRE)
The SEL-351 provides user-programmable event report length and prefault
length. Event report length is either 15 or 30 cycles. Prefault length ranges
from 1 to 29 cycles. Prefault length is the first part of the event report that
precedes the event report triggering point.
Set the event report length with the LER setting. Set the prefault length with
the PRE setting. See the
SET G
and corresponding
Event Report Parameters (See Section 12) on page SET.24
for instructions on
setting the LER and PRE settings.
Changing the LER setting will erase all events stored in nonvolatile memory.
Changing the PRE setting has no effect on the nonvolatile reports.
Standard Event
Report Triggering
The relay triggers (generates) a standard event report when any of the
following occur:
➤
Relay Word bit TRIP asserts
➤
Programmable SEL
OGIC®
control equation setting ER asserts
to logical 1
➤
TRI
(Trigger Event Reports) serial port command executed
➤
Output contacts
OUT101
–
OUT107
(Models 0351
x
0, 0351
x
1, and
0351
x
Y) pulsed via the serial port or front-panel
PUL
(Pulse
Output Contact) command
Relay Word Bit TRIP
. If Relay Word bit TRIP asserts to logical 1, an event
report is automatically generated. Thus, any condition that causes a trip does
not have to be entered in SEL
OGIC
control equation setting ER.
For example, SEL
OGIC
control equation trip setting TR is unsupervised. Any
trip condition that asserts in setting TR causes the TRIP Relay Word bit to
assert immediately. The factory setting for trip setting TR is:
TR =
51PT + 51GT + 81D1T + LB3 + 50P1 * SH0
If any of the individual conditions 51PT, 51GT, 81D1T, LB3, or 50P1 * SH0
assert, Relay Word bit TRIP asserts, and an event report is automatically
generated. Thus, these conditions do not have to be entered in SEL
OGIC
control equation setting ER.
Relay Word bit TRIP (in
) is usually assigned to an output contact
for tripping a circuit breaker (e.g., SEL
OGIC
control equation setting
OUT101 = TRIP).
NOTE:
is on multiple
pages.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...