7.31
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Inputs, Outputs, Timers, and Other Control Logic
SEL
OGIC
Control Equation Variables/Timers
Preceding
shows an effective seal-in logic circuit, created by use
of Relay Word bit SV7 (SEL
OGIC
control equation variable SV7) in SEL
OGIC
control equation SV7:
SV7 =
(SV7 + IN101) * (50P1 + 50N1)
If power is lost to the relay, settings are changed (for the active setting group),
or the active setting group is changed, the seal-in logic circuit is “broken” by
virtue of Relay Word bit SV7 being reset to logical 0 (assuming input
IN101
is
not asserted). Relay Word bit SV7T is also reset to logical 0, and timer
settings SV7PU and SV7DO load up again.