B.7
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Firmware Upgrade Instructions
Relay Firmware Upgrade Instructions
Enter Access Level 2
Step 1. Type
ACC <Enter>
at the Access Level 0
=
prompt.
Step 2. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1
=>
prompt.
Step 3. Type
2AC <Enter>
.
Step 4. Type the Access Level 2 password and press
<Enter>
.
You will see the Access Level 2
=>>
prompt.
Backup Relay Settings
The relay preserves settings and passwords during the firmware upgrade
process. However, interruption of relay power during the upgrade process can
cause the relay to lose settings. Make a copy of the original relay settings in
case you need to reenter the settings. Use either the SEL-5010 Relay Assistant
software or
AC
SEL
ERATOR
QuickSet
to record the existing relay settings and
proceed to
. Otherwise, perform the following steps:
Step 1. From the
Transfer
menu in
HyperTerminal
, select
Capture
Text
.
Step 2. Enter a directory and filename for a text file where you will
record the existing relay settings.
Step 3. Click
Start
.
The
Capture Text
command copies all the information you
retrieve and all the keystrokes you type until you send the
command to stop capturing text. The terminal emulation
program stores these data in the text file.
Step 4. Execute the Show Calibration (
SHO C
) command to retrieve
the relay calibration settings.
Use the following Show commands to retrieve the relay
settings:
SHO G
,
SHO 1
,
SHO L 1
,
SHO 2
,
SHO L 2
,
SHO 3
,
SHO L 3
,
SHO 4
,
SHO L 4
,
SHO 5
,
SHO L 5
,
SHO 6
,
SHO L 6
,
SHO P 1
,
SHO P 2
,
SHO P 3
,
SHO P F
,
SHO R
, and
SHO T
.
NOTE:
Settings classes can vary
among SEL relays. See the relay
instruction manual for a listing.
Step 5. From the
Transfer
menu in
HyperTerminal
, select
Capture
Text
and click
Stop
.
The computer saves the text file you created to the directory
you specified in
under
Step 6. Write down the present relay data transmission setting
(SPEED).
This setting is SPEED in the
SHO P
relay settings output. The
SPEED value should be the same as the value you recorded in
A. Prepare the Relay on page B.2
.
D. Start SEL
BOOT
Step 1. Find and record the firmware identification string (FID):
a. From the
File
menu, choose
Properties
.
b. Select the
Settings
tab in the
Properties
dialog box
NOTE:
If the relay does not prompt
you for Access Level 1 and Access
Level 2 passwords, check whether the
relay has a password jumper in place.
With this jumper in place, the relay is
unprotected from unauthorized
access (see the relay instruction
manual).
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...