L.12
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
SEL Synchrophasors
View Synchrophasors by Using the MET PM Command
View Synchrophasors by Using the
MET PM Command
The
MET PM
serial port ASCII command may be used to view the SEL-351
synchrophasor measurements. See
MET Command (Metering Data) on
for general information on the
MET
command.
There are multiple ways to use the
MET PM
command:
➤
As a test tool, to verify connections, phase rotation, and
scaling.
➤
As an analytical tool, to capture synchrophasor data at an exact
time, in order to compare this information with similar data
captured in other phasor measurement unit(s) at the same time.
➤
As a method of periodically gathering synchrophasor data
through a communications processor.
The
MET PM
command displays the same set of analog synchrophasor
information, regardless of the Global settings PHDATAV and PHDATAI. The
MET PM
command can function even when no serial ports are sending fast
message synchrophasor data.
The
MET PM
command only displays data when the Relay Word bit TSOK =
logical 1.
shows a sample
MET PM
command response. The
synchrophasor data are also available in
AC
SEL
ERATOR
QuickSet and have a
.
The
MET PM [
time
]
command can be used to direct the SEL-351 to display
the synchrophasor for an exact specified time, in 24-hour format. For example,
entering the command
MET PM 14:14:12
will result in a response similar to
occurring just after 14:14:12, with the time stamp 14:14:12.000.
This method of data capture always reports from the exact second, even if the
time parameter is entered with fractional seconds. For example, entering
MET
PM 14:14:12.200
results in the same data capture as
MET PM 14:14:12
,
because the relay ignores the fractional seconds.
See
MET PM—Synchrophasor Metering on page 10.25
for complete
command options, and error messages.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...