6.27
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Close and Reclose Logic
Reclosing Relay
Additional Settings Example 1
With sequence coordination setting:
79SEQ =
79RS * 51P
sequence coordination is operable only when the relay is in the Reset State
(79RS = logical 1). Refer to
Figure 6.8
Sequence Coordination Between the SEL-351 and a Line Recloser
Assume that the line recloser is set to operate twice on the fast curve and then
twice on the slow curve. The slow curve is allowed to operate after two fast
curve operations because the fast curves are then inoperative for tripping. The
SEL-351 phase time-overcurrent element 51PT is coordinated with the line
recloser fast curve. The SEL-351 single-phase time-overcurrent elements
51AT, 51BT, and 51CT are coordinated with the line recloser slow curve.
Fast Curve
(Line Recloser)
51P1
Slow Curve
(Line Recloser)
t
I
F
I
51P1T
(SEL-351)
51AT, 51BT, 51CT
(SEL-351)
SEL-351
R
Line Recloser
I
F
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...