F.7
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Setting Negative-Sequence Overcurrent Elements
Coordinating Negative-Sequence Overcurrent Elements
element, whether it operates faster or slower than its complementary ground
overcurrent element, will operate faster than the upstream negative-sequence
overcurrent element for all faults, including those that involve ground.