12.14
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Standard 15/30-Cycle Event Reports
27 PP2
(delta-connected)
27AB2, 27BC2,
27CA2
A
AB phase-to-phase instantaneous undervoltage element 27AB2 picked up.
B
BC phase-to-phase instantaneous undervoltage element 27BC2 picked up.
C
CA phase-to-phase instantaneous undervoltage element 27CA2 picked up.
a
27AB2 and 27CA2 elements picked up.
b
27AB2 and 27BC2 elements picked up.
c
27BC2 and 27CA2 elements picked up.
3
27AB2, 27BC2 and 27CA2 elements picked up.
27 S
27S
*
Channel VS instantaneous undervoltage element 27S picked up.
59 P
(wye-connected)
59A1, 59A2, 59B1,
59B2, 59C1, 59C2
A
A-phase instantaneous overvoltage element 59A1 or 59A2 picked up.
B
B-phase instantaneous overvoltage element 59B1 or 59B2 picked up.
C
C-phase instantaneous overvoltage element 59C1 or 59C2 picked up.
a
59A_ and 59B_ elements picked up.
b
59B_ and 59C_ elements picked up.
c
59C_ and 59A_ elements picked up.
3
59A_, 59B_ and 59C_ elements picked up.
59 PP
59AB, 59BC, 59CA
A
AB phase-to-phase instantaneous overvoltage element 59AB picked up.
B
BC phase-to-phase instantaneous overvoltage element 59BC picked up.
C
CA phase-to-phase instantaneous overvoltage element 59CA picked up.
a
59AB and 59CA elements picked up.
b
59AB and 59BC elements picked up.
c
59BC and 59CA elements picked up.
3
59AB, 59BC and 59CA elements picked up.
59 PP2
(delta-connected)
59AB2, 59BC2,
59CA2
A
AB phase-to-phase instantaneous overvoltage element 59AB2 picked up.
B
BC phase-to-phase instantaneous overvoltage element 59BC2 picked up.
C
CA phase-to-phase instantaneous overvoltage element 59CA2 picked up.
a
59AB2 and 59CA2 elements picked up.
b
59AB2 and 59BC2 elements picked up.
c
59BC2 and 59CA2 elements picked up.
3
59AB2, 59BC2 and 59CA2 elements picked up.
59 V1Q
(wye-connected)
59V1, 59Q
1
Positive-sequence instantaneous overvoltage element 59V1 picked up.
Q
Negative-sequence instantaneous overvoltage element 59Q picked up.
b
Both 59V1 and 59Q picked up.
59 V1
(delta-connected)
59V
*
Positive-sequence instantaneous overvoltage element 59V1 picked up.
59 Q
(delta-connected)
59Q, 59Q2
1
Negative-sequence instantaneous overvoltage element 59Q picked up.
2
Negative-sequence instantaneous overvoltage element 59Q2 picked up.
b
Both 59Q and 59Q2 picked up.
Table 12.3
Output, Input, and Protection, and Control Element Event Report Columns
(Sheet 4 of 10)
Column Heading
Corresponding
Elements (Relay
Word Bits)
Symbol
Definition
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...