B.5
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Firmware Upgrade Instructions
Relay Firmware Upgrade Instructions
Figure B.4
Setting Terminal Emulation
Step 8. Confirm serial communication.
Press
<Enter>
. In the terminal emulation window, you should
see the Access Level 0
=
If this is successful, proceed to
Figure B.5
Terminal Emulation Startup Prompt
Failure to Connect
If you do not see the Access Level 0
=
prompt, press
<Enter>
again. If you
still do not see the Access Level 0
=
prompt, you have either selected the
incorrect serial communications port on the computer, or the computer speed
setting does not match the data transmission rate of the relay. Perform the
following steps to reattempt a connection:
Step 9. From the
Call
menu, choose
Disconnect
to terminate
communication.
Step 10. Correct the port setting:
a. From the
File
menu, choose
Properties
.
You should see a dialog box similar to
.
b. Select a different port in the
Connect using
list box.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...