12.15
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Standard Event Reports, Sag/Swell/Interruption Report, and SER
Standard 15/30-Cycle Event Reports
59 N
(wye-connected)
59N1, 59N2
1
Zero-sequence instantaneous overvoltage element 59N1 picked up.
2
Zero-sequence instantaneous overvoltage element 59N2 picked up.
b
Both 59N1 and 59N2 picked up.
59 S
59S1, 59S2
1
Channel VS instantaneous overvoltage element 59S1 picked up.
2
Channel VS instantaneous overvoltage element 59S2 picked up.
b
Both 59S1 and 59S2 picked up.
59 V
59VP, 59VS
P
Phase voltage window element 59VP picked up
(used in synchronism check).
S
Channel VS voltage window element 59VS picked up
(used in synchronism check).
b
Both 59VP and 59VS picked up.
25 SF
SF
*
Slip frequency element SF picked up (used in synchronism check).
25 A
25A1, 25A2
1
Synchronism check element 25A1 element picked up.
2
Synchronism check element 25A2 element picked up.
b
Both 25A1 and 25A2 picked up.
81 27B
27B81
*
Frequency logic instantaneous undervoltage element 27B81 picked up.
81 12
81D1, 81D2
1
Frequency element 81D1 picked up.
2
Frequency element 81D2 picked up.
b
Both 81D1 and 81D2 picked up.
81 34
81D3, 81D4
3
Frequency element 81D3 picked up.
4
Frequency element 81D4 picked up.
b
Both 81D3 and 81D4 picked up.
81 56
81D5, 81D6
5
Frequency element 81D5 picked up.
6
Frequency element 81D6 picked up.
b
Both 81D5 and 81D6 picked up.
79
RCSF, CF, 79RS,
.
Reclosing relay nonexistent.
79CY, 79LO
S
Reclose supervision failure condition (RCSF asserts for only 1/4 cycle).
F
Close failure condition (CF asserts for only 1/4 cycle).
R
Reclosing relay in Reset State (79RS).
C
Reclosing relay in Reclose Cycle State (79CY).
L
Reclosing relay in Lockout State (79LO).
Time
OPTMN, RSTMN
o
Recloser open interval timer is timing.
r
Recloser reset interval timer is timing.
Shot
SH0, SH1, SH2
.
Reclosing relay nonexistent.
SH3, SH4
0
shot = 0 (SH0).
1
shot = 1 (SH1).
2
shot = 2 (SH2).
3
shot = 3 (SH3).
4
shot = 4 (SH4).
Table 12.3
Output, Input, and Protection, and Control Element Event Report Columns
(Sheet 5 of 10)
Column Heading
Corresponding
Elements (Relay
Word Bits)
Symbol
Definition
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...