8.15
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Breaker Monitor, Metering, and Load Profile Functions
Station DC Battery Monitor
Station DC Battery Monitor
The station dc battery monitor in the SEL-351 can alarm for under- or
overvoltage dc battery conditions and give a view of how much the station dc
battery voltage dips when tripping, closing, and other dc control functions
take place. The monitor measures the station dc battery voltage applied to the
rear-panel terminals labeled
POWER
(see
, and
). The station dc battery monitor settings (DCLOP and DCHIP) are
available via the
SET G
command (see
and also
Monitor (See Figure 8.9 and Figure 8.10) on page SET.25
DC Under- and
Overvoltage
Elements
. The station dc battery monitor compares the measured
station battery voltage (Vdc) to the undervoltage (low) and overvoltage (high)
pickups DCLOP and DCHIP. The setting range for pickup settings DCLOP
and DCHIP is:
20 to 300 Vdc, 1 Vdc increments
This range allows the SEL-351 to monitor nominal battery voltages of 24, 48,
110, 125, 220, and 250 V. When testing the pickup settings DCLOP and
DCHIP,
do not
operate the SEL-351 outside of its power supply limits. See the
Specifications subsection
for the various power supply
specifications. The power supply rating is located on the serial number sticker
on the relay rear panel.
Figure 8.9
DC Under- and Overvoltage Elements
Logic outputs DCLO and DCHI in
operate as follows:
Create Desired Logic
for DC Under- and
Overvoltage Alarming
Pickup settings DCLOP and DCHIP are set independently. Thus, they can be
set:
DCLOP < DCHIP or DCLOP > DCHIP
shows the resultant dc voltage elements that can be created with
SEL
OGIC
control equations for these two setting cases. In these two examples,
the resultant dc voltage elements are time-qualified by timer SV4T and then
routed to output contact
OUT106
for alarm purposes.
DCLO = 1 (logical 1), if V
dc
≤
pickup setting DCLOP
= 0 (logical 0), if V
dc
> pickup setting DCLOP
DCHI = 1 (logical 1), if V
dc
≥
pickup setting DCHIP
= 0 (logical 0), if Vdc < pickup setting DCHIP
DCLO
DCHI
V
dc
Relay
Word
Bits
DCLOP
DCHIP
Settings
Undervoltage
Overvoltage
(From Rear-Panel
Terminals Labeled
POWER
)
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...