B.21
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Firmware Upgrade Instructions
Ethernet Port Firmware Upgrade Instructions
D. Establish a Telnet Connection
To establish a Telnet-to-card connection, perform the following steps.
Step 1. Click
Start > Run
.
Step 2. Type
cmd
in the dialog box, and press
<Enter>
to launch a
DOS command window.
Step 3. Type
Telnet <IP Address> port
at the prompt (e.g.,
Telnet
10.201.0.213 1024
).
Step 4. Press
<Enter>
several times until you see the
=
prompt.
E. Verify Firmware Transfer
To verify the firmware transfer completed properly, perform the following
steps after establishing a Telnet connection.
Step 1. Issue a
STA
command.
Step 2. Verify that the
STA
report does not include any warnings or
failures.
Step 3. Verify that the
STA
report includes
Device Enabled
at the end
of the report.
Step 4. Verify that the
STA
report FID matches the FID of the
firmware you transferred.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...