6.3
Date Code 20070117
Instruction Manual
SEL-351-5, -6, -7 Relay
Close and Reclose Logic
Close Logic
The
CLOSE
(CC) command is not embedded in the close logic. It is included
in the factory SEL
OGIC
control equation settings:
CL =
… + CC
Relay Word bit CC asserts for execution of the
CLOSE
command. See
Command (Close Breaker) on page 10.36
for more information on the
CLOSE
command. More discussion follows later on the factory settings for
setting CL.
If a user wants to supervise the
CLOSE
command with optoisolated input
IN106
, the following setting is made:
CL =
… + CC * IN106
With this setting, the
CLOSE
command can provide a close only if
optoisolated input
IN106
is asserted. This is just one
CLOSE
command
supervision example—many variations are possible.
Unlatch Close
If the CLOSE Relay Word bit is asserted at logical 1, it stays asserted at
logical 1 until one of the following occurs:
➤
The unlatch close condition asserts (ULCL = logical 1).
➤
The circuit breaker closes (52A = logical 1).
➤
The reclose initiation condition (79RI) makes a rising-edge
(logical 0 to logical 1) transition.
➤
The Close Failure Timer times out (Relay Word bit CF = 1).
The Close Failure Timer is inoperative if setting CFD = OFF.
Factory Settings
Example
The factory settings for the close logic SEL
OGIC
control equation settings are:
52A =
IN101
CL =
LB4 + CC
ULCL =
TRIP
The factory setting for the Close Failure Timer setting is:
CFD =
60.00 cycles
See the
SEL-351-5, -6, -7 Relay Settings Sheets
for setting ranges.
Set Close
If the Reclosing Relay Open Interval Time-Out logic input at the top of
is ignored (reclosing is discussed in detail in a following
subsection), then SEL
OGIC
control equation setting CL is the only logic input
that can set the CLOSE Relay Word bit.
In SEL
OGIC
control equation setting CL = LB4 + CC
➤
Local bit LB4 operates as a manual close switch via the front
panel. See
Local Control Switches on page 7.6
for more information on local control.
➤
Relay Word bit CC asserts for execution of the
CLOSE
CLO Command (Close Breaker) on page 10.36
for more information on the
CLOSE
command.
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...